Details

Title Pump-hose systems with universal fire barrels for extinguishing buildings // Magazine of Civil Engineering. – 2021. – № 3 (103). — С. 10305
Creators Marozau A. A. ; Tran Duc H. ; Kamluk A. N. ; Parmon V. V. ; Striganova M. Yu.
Imprint 2021
Collection Общая коллекция
Subjects Энергетика ; Гидравлические машины ; pump-hose systems ; hydraulic calculations ; experimental research ; hydraulic resistance ; numerical methods ; universal fire barrels ; fighting fire ; насосно-шланговые системы ; гидравлические расчеты ; экспериментальные исследования ; гидравлическое сопротивление ; численные методы ; универсальные пожарные стволы ; борьба с огнем
UDC 621.22
LBC 31.56
Document type Article, report
File type PDF
Language English
DOI 10.34910/MCE.103.5
Rights Свободный доступ из сети Интернет (чтение, печать, копирование)
Record key RU\SPSTU\edoc\67129
Record create date 7/14/2021

Allowed Actions

Read Download (0.8 Mb)

Group Anonymous
Network Internet

The hydraulic calculation of pump-hose system was carried out, taking into account the influence of its elements on the performance of fire barrels. Corresponding dependences for mixed pump-hose systems consisting of one and three fire barrels are presented. Based on the hydraulic calculation of the pump-hose system, it was found that an increase in the number of hoses to 12 in the main and up to 3 in the working line leads to a decrease in barrel consumption by 1,5 %, which does not affect fire fighting process. As a result of the analysis of the pump-hose system with three fire barrels when changing the main parameters in one of them, we can conclude that a significant effect on the flow rate is exerted by a change in the position of the dispenser, the height of the barrel and the number of hoses in the working line (total line resistance). It was also established that the flow rate of the other two system trunks varies slightly (1,5 %), which in practice can be ignored. Based on the data obtained, recommendations are given to the operator working on the pump of a fire truck when feeding fire extinguishing substances to a height. The presented research results are obtained in the field of fire extinguishing agents and methods of their application and can be used in fire fighting and emergency response.

Network User group Action
ILC SPbPU Local Network All
Read Print Download
Internet All
  • 1. Introduction
  • 2. Methods
  • 3. Results and Discussion
  • 4. Conclusions

Access count: 307 
Last 30 days: 17

Detailed usage statistics