Details

Title: Электрическая часть КЭС мощностью 4х500 МВт: выпускная квалификационная работа магистра: направление 13.04.02 «Электроэнергетика и электротехника» ; образовательная программа 13.04.02_01 «Электроэнергетические установки электрических станций и подстанций»
Creators: Кузнецов Павел Владимирович
Scientific adviser: Шахова Мария Алексеевна
Other creators: Соловьева Светлана Николаевна
Organization: Санкт-Петербургский политехнический университет Петра Великого. Институт энергетики
Imprint: Санкт-Петербург, 2021
Collection: Выпускные квалификационные работы; Общая коллекция
Subjects: Турбогенераторы; Трансформаторы; Токи короткого замыкания; Электрические станции; распределительное устройство; switchgear
UDC: 621.313.322; 621.314.21/.24; 621.311.2
Document type: Master graduation qualification work
File type: PDF
Language: Russian
Level of education: Master
Speciality code (FGOS): 13.04.02
Speciality group (FGOS): 130000 - Электро- и теплоэнергетика
Links: Отзыв руководителя; Рецензия; Отчет о проверке на объем и корректность внешних заимствований
DOI: 10.18720/SPBPU/3/2021/vr/vr21-5937
Rights: Доступ по паролю из сети Интернет (чтение, печать, копирование)
Record key: ru\spstu\vkr\16037

Allowed Actions:

Action 'Read' will be available if you login or access site from another network Action 'Download' will be available if you login or access site from another network

Group: Anonymous

Network: Internet

Annotation

Цель работы: разработать и рассчитать электрическую часть конденсационной электростанции с 4 генераторами номинальной мощностью 500 МВт каждый. Задачи, которые решались в ходе выполнения выпускной квалификационной работы: 1. Разработана и рассчитана электрическая часть конденсационной электростанции с 4 генераторами номинальной мощностью 500 МВт каждый. 2. Выбрана структурная схема станции и основное силовое оборудование: турбогенератор, блочный повышающий трансформатор, автотрансформатор, трансформатор собственных нужд, резервный трансформатор собственных нужд. 3. Выбрана схема собственных нужд с учетом рабочего и резервного питания. 4. Произведен выбор схем распределительных устройств повышенных напряжений с учетом числа присоединений для РУ-500 кВ выбрано РУ типа «Двойная система сборных шин с тремя выключателями на два присоединения» (3/2), для РУ 220 кВ выбрано РУ типа «Двойная несекционированная система сборных шин с обходной системой сборных шин с одним выключателем на присоединение». 5. Рассчитаны токи трёхфазных коротких замыканий в 6 точках схемы станции. На основании расчетов токов короткого замыкания, был выполнен выбор коммутационных аппаратов, токоведущих частей, измерительных трансформаторов тока и напряжения станции. 6. Рассмотрены основные технические решения по системе релейной защиты блоков генератор-трансформатор станции. Результатом работы является проект электрической части КЭС, включающий пояснительную записку с обосновывающими расчетами, чертежи главной схемы электрических соединений станции, схемы собственных нужд, схемы заполнения ОРУ 500 кВ, плана ОРУ 500 кВ, разреза по ячейке ОРУ 500 кВ.

The purpose of the work is to develop and calculate the electrical part of a condensation power plant with 4 generators with a capacity of 500 MW each. The following tasks were solved in the course of the work: 1. In this work, the electrical part of the condensation power plant with a capacity of 4x500 MW has been developed and calculated. 2. The block diagram of the plant and the main power equipment included: a turbine TVV-500-2EU3 generator, block step-up TC-630000/500 and TC-630000/220 transformers, an ATDTSN-500000/500/220 auto-transformer, an auxiliary TRDNS-63000/35 transformer, a standby auxiliary TRDCN-63000/220 transformer. 3. The scheme of auxiliaries was developed, taking into account the working and backup power supply. 4. High-voltage switchgear circuits were selected, taking into account the number of connections. Double bus bar system with three switches for two connections (3/2) was selected for switchgear 500 kV, and Double non-partitioned bus bar system with a bypass bus bar system with one switch per connection was selected for switchgear 220 kV. 5. Three-phase short-circuit currents were calculated at 6 points of the plant circuit. Based on the calculations of short-circuit currents, the selection of switching devices, live parts, measuring current and voltage transformers of the plant was made. 6. The main design solutions for the relay protection system of the generator-transformer blocks of the plant were considered. The result of the work is a project of the electrical part of the condensation power plant, which includes the explanatory note with the calculations and drawings of the main electrical connection diagram of the plant, auxiliaries diagrams, a scheme for filling the 500 kV outdoor switchgear, a 500 kV outdoor switchgear plan, a section for a 500 kV outdoor switchgear cell.

Document access rights

Network User group Action
ILC SPbPU Local Network All Read Print Download
Internet Authorized users SPbPU Read Print Download
-> Internet Anonymous

Table of Contents

  • Содержание
  • Введение
  • 1.1. Выбор генератора.
  • 1.2. Выбор структурной схемы электростанции.
  • 1.3. Расчет перетоков мощности по основным элементам электрооборудования.
  • 1.4. Выбор блочных повышающих трансформаторов.
  • 1.5. Выбор автотрансформаторов связи.
  • 1.6. Выбор рабочего трансформатора собственных нужд.
  • 1.7. Выбор резервного трансформатора собственных нужд.
  • 2.1. Выбор схемы собственных нужд.
  • 2.2. Выбор схем распределительных устройств повышенных напряжений.
  • Глава 3. Расчет токов короткого замыкания.
  • 3.1. Составление схемы замещения
  • 3.2. Выбор базисных условий
  • 3.3. Расчет параметров элементов схемы замещения
  • 3.4. Преобразование схем замещения к простейшему виду и расчет токов короткого замыкания.
  • 3.5. Расчет тока короткого замыкания в точке К1.
  • 3.7. Расчет тока короткого замыкания в точке К3.
  • 3.8. Расчет тока короткого замыкания в точке К4.
  • 3.9. Расчет тока короткого замыкания в точке К5.
  • 3.10. Расчет тока короткого замыкания в точке К6.
  • 4.1. Выбор выключателей и разъединителей
  • 4.2. Выбор выключателей РУ высокого напряжения
  • 4.3. Выбор разъединителей РУ высокого напряжения
  • 4.4. Выбор генераторных выключателей
  • 4.5. Выбор токопроводов на генераторном напряжении
  • 4.6. Выбор отпайки от генераторного токопровода к ТСН
  • 4.7.Выбор трансформаторов тока
  • 4.8. Выбор трансформаторов напряжения
  • 4.8. Выбор выключателей и ячеек КРУ 6 кВ
  • 5.1. Основные технические требования к системе РЗА.
  • 5.2.Описание функций релейной защиты и выбор комплекта защит.
  • 5.3. Выбор микропроцессорного устройства для реализации защит.
  • Приложение №1
  • Чертеж:
  • Главная схема электрических соединений КЭС 4х500 МВт.
  • Приложение №2
  • Чертеж:
  • Схема собственных нужд КЭС 4х500 МВт
  • Приложение №3
  • Чертеж:
  • Схема заполнения ОРУ 500 кВ
  • Приложение №4
  • Чертеж:
  • Разрез по ячейке одного из ОРУ 500 кВ

Usage statistics

stat Access count: 19
Last 30 days: 0
Detailed usage statistics