Details
| Title | Дугогасительное устройство с камерой автогенерации 750 кВ, 50 кА: выпускная квалификационная работа бакалавра: направление 13.03.02 «Электроэнергетика и электротехника» ; образовательная программа 13.03.02_06 «Электрические и электронные аппараты» = Arc-Extinguishing Device with Self-Blast Chamber for 750 kV, 50 kA |
|---|---|
| Creators | Нурлигенов Андрей Сергеевич |
| Scientific adviser | Тонконогов Евгений Николаевич |
| Organization | Санкт-Петербургский политехнический университет Петра Великого. Институт энергетики |
| Imprint | Санкт-Петербург, 2026 |
| Collection | Выпускные квалификационные работы ; Общая коллекция |
| Subjects | высоковольтный выключатель ; автогенерационное дугогасительное устройство ; элегаз ; CO2/C4F7N отключающая способность ; high-voltage circuit breaker ; self-blast arc-extinguishing chamber ; SF₆ ; CO₂/C₄F₇N ; breaking capacity |
| Document type | Bachelor graduation qualification work |
| Language | Russian |
| Level of education | Bachelor |
| Speciality code (FGOS) | 13.03.02 |
| Speciality group (FGOS) | 130000 - Электро- и теплоэнергетика |
| DOI | 10.18720/SPBPU/3/2026/vr/vr26-2469 |
| Rights | Доступ по паролю из сети Интернет (чтение, печать) |
| Additionally | New arrival |
| Record key | ru\spstu\vkr\44116 |
| Record create date | 9/1/2026 |
Allowed Actions
–
Action 'Read' will be available if you login or access site from another network
| Group | Anonymous |
|---|---|
| Network | Internet |
Данная работа посвящена исследованию возможности использования альтернативного дугогасящего газа CO2/C4F7N и сравнению отключающей способности высоковольтных выключателей при использовании различных рабочих сред. В исследовании проведен анализ современных газовых выключателей, конструкции дугогасительного устройства с автогенерацией, требований к рабочим газам и параметры, влияющих на отключающую способность выключателей. Исследовано взаимодействие выключателя 750кВ, 50кА с сетью. На основании рассмотренных требований к рабочим газам в литературных источниках проведен поиск и сравнение газов и смесей газов, являющихся альтернативой элегазу. На основании проведенного комплексного анализа сделан выбор возможного альтернативного газа для дальнейшего исследования – CO2/C4F7N 90%/10%. В ходе работы проведен расчет геометрических параметров ДУ и анализ термодинамических параметров в дугогасительном устройстве с CO2/C4F7N-изоляцией и с элегазовой изоляцией. Был проведен анализ полей параметров дугогасящего газа в дугогасительном устройстве. На основании полученных зависимостей давления был проведен расчет отключающей способности высоковольтного выключателя при использовании смеси газов CO2/C4F7N и элегаза. Показана принципиальная возможность замены элегаза смесью газов CO2/C4F7N без дополнительных изменений геометрии проточной части дугогасительного устройства. Для достижения данных результатов в работе было использовано следующее программное обеспечение: Mathcad, COMSOL Multiphysics.
This work is devoted to the study of the possibility of using alternative arc-extinguishing gas CO₂/C₄F₇N and comparing the breaking capacity of high-voltage circuit breakers when using different working media. The study provides an analysis of modern gas circuit breakers, the design of a self-blast arc-extinguishing device, requirements for working gases, and parameters affecting the breaking capacity of circuit breakers. The interaction of a 750 kV, 50 kA circuit breaker with the power grid is investigated. Based on the requirements for working gases found in literature sources, a search and comparison of gases and gas mixtures that are alternatives to SF₆ has been carried out. Based on a comprehensive analysis, a possible alternative gas for further research was selected – CO₂/C₄F₇N 90%/10%. In the course of the work, the geometric parameters of the arc-extinguishing device (AED) were calculated, and the thermodynamic parameters in the arc-extinguishing device with CO₂/C₄F₇N insulation and with SF₆ insulation were analyzed. An analysis of the parameter fields of the arc-extinguishing gas in the arc-extinguishing device was carried out. Based on the obtained pressure dependences, the breaking capacity of the high-voltage circuit breaker when using the CO₂/C₄F₇N gas mixture and SF₆ was calculated. The fundamental possibility of replacing SF₆ with a CO₂/C₄F₇N gas mixture without additional changes to the flow path geometry of the arc-extinguishing device is demonstrated. The following software was used to obtain these results: Mathcad, COMSOL Multiphysics.
| Network | User group | Action |
|---|---|---|
| ILC SPbPU Local Network | All |
|
| Internet | Authorized users SPbPU |
|
| Internet | Anonymous |
|
- Введение.
- 1. Высоковольтные включатели 750кВ
- 1.1 Обзор существующих высоковольтных выключателей
- 1.2. Принцип работы дугогасительного устройства
- 1.3. Факторы, влияющие на гашение электрической дуги
- 1.4. Перспективы исследований высоковольтных выключателей
- 1.5. Исследование альтернативных элегазу дугогасящих и изолирующих газовых сред
- 1.6. Постановка задачи
- Вывод
- Глава 2. Взаимодействие высоковольтного выключателя 750 кВ, 50 кА с сетью при различных режимах работы
- 2.1. Анализ номинальных параметров выключателя
- 2.2. Расчет ПВН при НКЗ (90%,30%);
- 2.2.1 Расчет ПВН при отключении токов НКЗ для ,𝒑-∗.= 0,9
- 2.2.2 Расчет ПВН при отключении токов НКЗ для ,𝒑-∗.= 0,3
- 2.3 Анализ ПВН при КЗ 100% (при I=Iно и I=0,1Iно)
- 2.3.1 Ток отключения 𝐈=,𝐈-но.
- 2.3.2 Ток отключения 𝐈=𝟎.𝟏∙,𝐈-но.
- 2.4. Оценка влияния шунтирующей емкости на отключающую способность дугогасительного устройства при НКЗ
- Вывод
- Глава 3. Математическая модель анализа отключающей способности в автогенерационном дугогасительном устройстве
- 3.1. Моделирование динамики дугогасящего потока.
- 3.2. Моделирование динамики дугогасительного газа в пакете Comsol.
- Вывод
- Часть 4. Анализ дугогасительной способности автогенерационного
- дугогасительного устройства 750 кВ, 50 кА
- 4.1. Расчет геометрических характеристик дугогасительного устройства
- 4.2. Анализ полей параметров дугогасящего газа в дугогасительном устройстве
- 4.2.1 Анализ режима холостого хода
- 4.2.2 Анализ режима короткого замыкания
- 4.2.3 Анализ полей для режима короткого замыкания
- 4.3 Расчет отключающей способности для двух газов
- Вывод
- ЗАКЛЮЧЕНИЕ
- СПИСОК ИСПОЛЬЗОВАННЫХ ИСТОЧНИКОВ